DRA Series
AC Power DIN-Mounted SPD with Replaceable Mods
The Meter-Treater DRA Series of Surge Protection Devices (SPDs) are single pole, parallel connected (MOV based technology) Type 1 CA (component assembly) protectors. Designed for use in both Type 1 and 2 locations these units are ANSI/UL 1449 Recognized. Each protector module provides 50 kA of Surge protection in a maintenance free, standard DIN profile, DIN Rail mountable, IP20 enclosure.
Benefits
DIN Rail mountable surge protection devices
Replaceable SPD modules eliminate costly, time-consuming replacement wiring ?
Simple snap "in/out"design for module replacement ?
Compact & lightweight yet rugged
Visual monitor advises protection status
Model choices allow for single mode or all-mode protection strategies
Each protector module's fixed base is "keyed" to ensure proper application
All protectors (except N-G model) are equipped with signaling contacts for remote monitoring of protection status

3D Preview
Load Current | Max Surge Current (8/20) Iₘₐₓ | Short-Circuit Current Rating (SCCR) | Repetative Impulse Rating (Iₙ) | On/Off Status⬥ | Housing Rating | Product Weight | Product Dimensions | Most Current Industry Standards | Surge Technology | Connector Form/ Type | Connector Method | Interface | Operating Temperature | Operating Frequency | Fusing | Listings & Certifications | Enclosure | Max. Operating Voltage | Max. Clamp Voltage | Energy Rating/ Wire | Response Time | Warranty | Series Resistance | Peak Pulse Power | Line - Load Sensitive | Breakover Voltage: (Line - Ground) | Attenuation Margin | NEXT | Data Transfer Rate | Power Sum NEXT | Return Loss | ACR | Power Sum ACR | ARC -F | PSACRF | Mounting | Relative Humidity | Terminals | Max. Circuits Protected | Modes of Protection | Continuous Current | Follow Current | Wire Range | Feedback | Remote Alarm Contacts | Remote Alarm contact capability (Nominal Volts/ Nominal Amps) | Remote Alarm Wire Size | Included Accessories |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
50 kA | 200 kA | 20 kA | Fault Windows | [See EDR Series] | IP 20 | MOV | -40 ℉ to +185 ℉
(-40 ℃ to + 85 ℃) | 47-63 Hz (50/60 Hz Typ.) | Listed to ANSI/UL 94 V-0 | < 1 Nanosecond | 5 Year Limited Product Warranty | 35mm DIN-Rail | 95% noncondensing | MOV model: None, GDT model: 200A Self Cutoff | #6-#12 AWG Solid (#2 AWG max) Stranded (#4 AWG max) CU | NO/NC/C, Isolated Form C | AC: 250V/0.5A DC: 250V/0.1A | Max # 16 AWG |
Specifications
Specification | Value |
---|---|
Max Surge Current (8/20) Iₘₐₓ | 50 kA |
Short-Circuit Current Rating (SCCR) | 200 kA |
Repetative Impulse Rating (Iₙ) | 20 kA |
On/Off Status⬥ | Fault Windows |
Housing Rating | [See EDR Series] |
Most Current Industry Standards | IP 20 |
Surge Technology | MOV |
Operating Temperature | -40 ℉ to +185 ℉
(-40 ℃ to + 85 ℃) |
Operating Frequency | 47-63 Hz (50/60 Hz Typ.) |
Listings & Certifications | Listed to ANSI/UL 94 V-0 |
Response Time | < 1 Nanosecond |
Warranty | 5 Year Limited Product Warranty |
Mounting | 35mm DIN-Rail |
Relative Humidity | 95% noncondensing |
Follow Current | MOV model: None, GDT model: 200A Self Cutoff |
Wire Range | #6-#12 AWG Solid (#2 AWG max) Stranded (#4 AWG max) CU |
Remote Alarm Contacts | NO/NC/C, Isolated Form C |
Remote Alarm contact capability (Nominal Volts/ Nominal Amps) | AC: 250V/0.5A DC: 250V/0.1A |
Remote Alarm Wire Size | Max # 16 AWG |
Diagrams
Not To Scale
Electrical Ratings
Click on any DRA Series model from the table to request a quote
Model Number | Service Voltage | TYPE | MCOV | # of Poles | L-N (MCOV) | L-G (MCOV) | N-G (MCOV) | L-N (VPR) | L-G (VPR) | N-G (VPR) | DIN Rail |
---|---|---|---|---|---|---|---|---|---|---|---|
DRA50-1P120-S | Single Phase 120V | AC | 150V | 1 | 150V | 150V | N/A | 700V | 700V | N/A | ✓ |
DRA50-1P220-S | Single Phase 220V | AC | 275V | 1 | 275V | 275V | N/A | 1000V | 1000V | N/A | ✓ |
DRA50-1P480-S | Single Phase 480V | AC | 550V | 1 | 550V | 550V | N/A | 1800V | 1800V | N/A | ✓ |
DRA50-2P120-LNG-S | 1Phase 120V | AC | 150V | 2 | 150V | N/A | 150V | 700V | N/A | 900V | ✓ |
DRA50-2P277-LGN-S | 1Phase 277V | AC | 320V | 2 | N/A | 320V | 320V | N/A | 1200V | 1200V | ✓ |
DRA50-2PS127-S | 2Phase 120/240V | AC | 180V | 2 | 180V | 180V | N/A | 1000V | 1000V | N/A | ✓ |
DRA50-2PS240-S | 2Phase 240/480V | AC | 320V | 2 | 320V | 320V | N/A | 1200V | 1200V | N/A | ✓ |
DRA50-3P240-S | 3Phase 240V | AC | 320V | 3 | N/A | 320V | N/A | N/A | 1200V | N/A | ✓ |
DRA50-3P480-S | 3Phase 480V | AC | 550V | 3 | N/A | 550V | N/A | N/A | 1800V | N/A | ✓ |
DRA50-3PS127-S | 2Phase 120/240V | AC | 180V | 3 | 180V | 180V | 180V | 1000V | 1000V | 1000V | ✓ |
DRA50-4P120-S | 3Phase 120/208V | AC | 150V | 4 | N/A | 150V | 150V | N/A | 700V | 700V | ✓ |
DRA50-4P277-S | 3Phase 277/480V | AC | 320V | 4 | N/A | 320V | 320V | N/A | 1200V | 1200V | ✓ |
Gas Discharge Tube is used in LNG units
Note: For Canadian applications add a "/C" at the end of the Model Number
⬥ Window Fault Indicator: Red = Service, Green = Good
Compatibility Table
EDR Model Number | PVA50-1P-xxxv-S | PVA50-2P-xxxv-S | PVA50-3P-xxxy-S | PVA50-5P-xxxy-S | DRA50-1Pxxx-S | DRA50-2Pxxx-LGN | DRA50-2Pxxx-S | DRA50-3Pxxx-S | DRA50-3PSxxx-S | DRA50-4Pxxx-S | CLT-xxx | SLT CAT X/X-POE | SLT/XM-02- | SLT/XM-04- | SLT/XM-06- | SLT/XM-10- | TST010/XXX | TST020/(120-250v) | TST020/(24-48v) | TST040/XXX |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|