TST Series

Commercial & Light Industrial DIN-Mounted SPD

The TST Series of SPDs (surge protection devices) are designed to protect sensitive electronic equipment from the harmful effects of transients.

Models are configured for both parallel or series installation and can be either din rail or wall mounted. Units are rated as Type 2 SPDs component assembly making the TST Series the ideal choice for incorporation into control cabinets for sensitive microelectronic based equipment.

TST units are self-contained in rugged plastic enclosures and use twenty millimeter (20mm) MOVs as their key suppression elements. Units are not line load sensitive and interface with the incoming power cables via screw terminals (barrier strips):

Small Terminals are capable of handling #14 to #30 AWG Wire.

Large Terminals are capable of handling #6 to #20 AWG Wire.

Devices are designed to protect sensitive electronic equipment from the harmful effects of transients.
Commercial
Industrial
Residential
Power

Power

3D Preview

Load Current
Max Surge Current (8/20) Iₘₐₓ
Short-Circuit Current Rating (SCCR)
Repetative Impulse Rating (Iₙ)
On/Off Status⬥
Housing Rating
Product Weight
Product Dimensions
Most Current Industry Standards
Surge Technology
Connector Form/ Type
Connector Method
Interface
Operating Temperature
Operating Frequency
Fusing
Listings & Certifications
Enclosure
Max. Operating Voltage
Max. Clamp Voltage
Energy Rating/ Wire
Response Time
Warranty
Series Resistance
Peak Pulse Power
Line - Load Sensitive
Breakover Voltage: (Line - Ground)
Attenuation Margin
NEXT
Data Transfer Rate
Power Sum NEXT
Return Loss
ACR
Power Sum ACR
ARC -F
PSACRF
Mounting
Relative Humidity
Terminals
Max. Circuits Protected
Modes of Protection
Continuous Current
Follow Current
Wire Range
Feedback
Remote Alarm Contacts
Remote Alarm contact capability (Nominal Volts/ Nominal Amps)
Remote Alarm Wire Size
Included Accessories
3-15A, 20-30A
10 - 40 kA per Phase (see models)
5 kA Symmetrical w/ external breaker, 100 kA Symmetrical w/external T Fuse
3 kA
LED
[See EDR Series]
16 Ounces
ANSI/UL 1449, 1283, CSA 22.2
MOV
Terminal Block
Terminal
-40 ℉ to +185 ℉ (-40 ℃ to + 85 ℃)
47-63 Hz (50/60 Hz Typ.)
Surge/ Thermal
Listed to ANSI/UL 94 V-0
Zytel (UL94 V-0) Polycarbonate
< 1 Nanosecond
15 Year Limited Product Warranty
35mm DIN or panel mount via 2 integrated tabs that accept up to #6 sized screws
95% noncondensing
Small Case: #30-#12 AWG, Large Case: #6-#20 AWG
NO/NC/C, Isolated Form C
24 AWG

Specifications

Specification
Value
Load Current
3-15A, 20-30A
Max Surge Current (8/20) Iₘₐₓ
10 - 40 kA per Phase (see models)
Short-Circuit Current Rating (SCCR)
5 kA Symmetrical w/ external breaker, 100 kA Symmetrical w/external T Fuse
Repetative Impulse Rating (Iₙ)
3 kA
On/Off Status⬥
LED
Housing Rating
[See EDR Series]
Product Weight
16 Ounces
Most Current Industry Standards
ANSI/UL 1449, 1283, CSA 22.2
Surge Technology
MOV
Connector Form/ Type
Terminal Block
Connector Method
Terminal
Operating Temperature
-40 ℉ to +185 ℉ (-40 ℃ to + 85 ℃)
Operating Frequency
47-63 Hz (50/60 Hz Typ.)
Fusing
Surge/ Thermal
Listings & Certifications
Listed to ANSI/UL 94 V-0
Enclosure
Zytel (UL94 V-0) Polycarbonate
Response Time
< 1 Nanosecond
Warranty
15 Year Limited Product Warranty
Mounting
35mm DIN or panel mount via 2 integrated tabs that accept up to #6 sized screws
Relative Humidity
95% noncondensing
Wire Range
Small Case: #30-#12 AWG, Large Case: #6-#20 AWG
Remote Alarm Contacts
NO/NC/C, Isolated Form C
Remote Alarm Wire Size
24 AWG

Diagrams 

Not To Scale

Electrical Ratings

Click on any TST Series model from the table to request a quote

Model Number
Service Voltage
L-N (VPR)
L-G (VPR)
N-G (VPR)
L-L (VPR)
DIN Rail
TST020/120-10-0-1/15A
120V
600
600
600
N/A
TST020/120-10-0-1/30A
120V
600
600
600
N/A
TST020/250-10-0-1/30A
250V
1000
1000
1000
N/A
TST040/024-2P-0-1/15A
24Vdc Positive, Negative, Gnd.
200
200
N/A
200
TST040/024-2P-0-1/30A
24Vdc Positive, Negative, Gnd.
200
200
N/A
200
TST040/048-2P-0-1/15A
48Vdc Positive, Negative, Gnd.
200
200
N/A
200
TST040/048-2P-0-1/30A
48Vdc Positive, Negative, Gnd.
200
200
N/A
200
TST040/120-10-0-1/15A
120V
500
500
600
N/A
TST040/120-10-0-1/30A
120V
500
500
600
N/A
TST040/220-10-0-1/15A
220V
800
800
800
N/A
TST040/220-10-0-1/30A
220V
800
800
800
N/A
TST040/250-10-0-1/15A
250V
800
800
800
N/A
TST040/250-10-0-1/30A
250V
800
800
800
N/A

Compatibility Table

EDR Model Number
PVA50-1P-xxxv-S
PVA50-2P-xxxv-S
PVA50-3P-xxxy-S
PVA50-5P-xxxy-S
DRA50-1Pxxx-S
DRA50-2Pxxx-LGN
DRA50-2Pxxx-S
DRA50-3Pxxx-S
DRA50-3PSxxx-S
DRA50-4Pxxx-S
CLT-xxx
SLT CAT X/X-POE
SLT/XM-02-
SLT/XM-04-
SLT/XM-06-
SLT/XM-10-
TST010/XXX
TST020/(120-250v)
TST020/(24-48v)
TST040/XXX
bottom of page